Fire Alarm System

  Fire Alarm Control Panel

   
Specification List

Item Content of Specification
Model QF-5AL QF-10AL
Total Zone 5 Zone 10 Zone
Input Power 220VAC 50/60HZ
Aux Power(Spare Battery) DC 24V 300mAH(NI-Cd Battery) DC 24V 600mAH(NI-Cd Battery)
Charging Voltage, Current DC 29V 60mA
Loop Voltage, Current Normal: DC 24V, Short-circuit: 5V, Under 32mA
Exterior Resistance Round-trip under 50Ω
Amount of Smoke Detectors Max. Amount of connection: 20/Loop
Amount of Heat Detectors No Limit (Except Electronic Type)
End of Line Resistance 10KΩ
Output Current for Indicating Lamp Max. Output Current: 120mA Max. Output Current: 240mA
Output Current for Alarm Bell Max. Output Current: 120mA Max. Output Current: 240mA
Case Material ABS resin with non-flammability
Auxiliary Contact I Null-Voltage Contact (N/O, 250VAC, 7A)


 

Fire Alarm Manual Push Button
Model
QF-1W(With Base for outdoor use)
QF-2W(indoor)
Voltage
DC-24V
DC-24V
Current
100mA
100mA
Contact Volume
DC-30V, 1A
DC-30V, 1A
Size
138mm x 70mm
138mm x 48mm
Weight
270g
150g

 

Fire Alarm Indicating Lamp(LED)
Model
QF-300L(With Base for outdoor use)
Voltage
DC-24V
Current
16mA (LED)
Color
Red
Size
95mm x 52mm
Weight
80g

 

Fire Alarm Bell (Motor Driven)
Model
QF-624B
QF-824B
QF-1024B
Gong Size
6inch
8inch
10inch
Voltage
24VDC
24VDC
24VDC
Current
20mA
20mA
20mA
Sound Level
95dB at 10ft
83dB at 10ft
85dB at 10ft

Features

  • Approved
  • High dBA sound output
  • Low power consumption
  • Available in 6", 8" and 10" Housing
  • Quickly and easily installed

Installation Note

  • Remove bell gong by loosening hex bolt
  • Wire bell in circuit (notice polarity)
  • Mount bell mechanism on 4" square standard outlet box with the striker facing down
  • Replace the gong and tighten hex bolt
  • The bell must be mounted a minimum of 8ft above the floor, or as close to the ceiling as possible
  • Polarized bell provides Red(-) and Black(+) lead wires. When you install the bell, must observe the polarity

BASIC MECHANISM AND GONGS

SMOKE DETECTOR

Features

  • With dual LED, easy to observe state of detector
  • The dual LED flash once every 4-6 seconds in peacetime to show if the detector works normally
  • The dual LED light up constantly when the detector alarms
  • With (-R) contact to connect to a remote indicating lamp to show alarm signal in different area
Specifications
Model No.
QF-202D
Overall Structure
Rate voltage
24VDC System from panel
Material
Fire-resisting ABS material
Standby current
35uA
Joint contact
Copper(Zinc-plated)
Alarm current
60mA
Color
Ivory
Working temperature
-15~50°C
notes:
Prohibit from being installed at the places with large volume of
smoke and steam lingering, and the inlet and outlet
of cold and warm air
Working humidity
0~95%RH
Size
103mm x 43mm
Weight
150g
   

Features

  • With dual LED, easy to observe state of detector
  • The dual LED flash once every 4-6 seconds in peacetime to show if the detector works normally
  • The dual LED light up constantly when the detector alarms
  • With (-R) contact to connect to a remote indicating lamp to show alarm signal in different area
Specifications
Model No.
QF-206
Overall Structure
Rate voltage
24VDC System from panel
Material
Fire-resisting ABS material
Standby current
90uA
Joint contact
Copper(Zinc-plated)
Alarm current
60mA
Color
Ivory
Working temperature
-15~50°C
notes:
Prohibit from being installed at the places with large volume of
smoke and steam lingering, and the inlet and outlet
of cold and warm air
Working humidity
0~95%RH
Size
103mm x 43mm
Weight
150g

HEAT DETECTOR

Features

  • Fix temperature : 60°C
  • With dual LED, easy to observe state of detector
  • The dual LED light up constantly when the detector alarms
  • With large metal surface to expose the air to sense the temperature
Specifications
Model No.
QF-407A
Overall Structure
Rate voltage
24VDC System from panel
Material
Fire-resisting ABS material
Standby current
0uA
Joint contact
Copper(Zinc-plated)
Alarm current
60mA
Color
Ivory
Working temperature
-15~50°C
Working humidity
0~95%RH
Size
103mm x 43mm
Weight
150g
   

Features

  • With dual LED, easy to observe state of detector
  • The dual LED flash once every 4-6 seconds in peacetime to show if the detector work normally
  • With large metal surface to expose the air to sense the temperature
Specifications
Model No.
QF-306A
Overall Structure
Rate voltage
24VDC System from panel
Material
Fire-resisting ABS material
Standby current
0uA
Joint contact
Copper(Zinc-plated)
Alarm current
60mA
Color
Ivory
Working temperature
-15~50°C
Working humidity
0~95%RH
Size
103mm x 43mm
Weight
150g
   

MANUAL CALL POINT

Features

  • Alarming by manual pressing
  • After pressing, glass break inside
  • With alarm indicating LED
  • Friendly installation and easy to replace glass
Specifications
Operating voltage
24VDC
Standby current
0mA
Alarm current
≤ 30mA(Equivalent resistance is 47Ω/1W)
Visual Indicator
Red illuminates and checking bar turn red after alarming
Application
Indoor use
Dimension (L x W x H)
97 x 93 x 49 mm(With back box)

Installation

  • Surface mounting :
    First install the back box onto the wall using screw
    Connect cable to manual call point body by shown in fig.1
    Combine the body and back box by tenon
  • flush mounting : it is not suitable
   

Remote Indicating Lamp

Features

This unit is designed to ensure that alarm signal can be actually transmitted to all locations. Especially for closed room, any fire inside can be indicate outside

Characteristics

  • Outstanding look from the design of art
  • Low current consumption
  • High intensity LED for quick identification
  • Larger indicating lamp lamp. (model AH-413)
  • Applicable for 12VDC and 24VDC (model AH-413)
  • Flash light is available for optional feature (model AH-413)
Specifications
Model
AH-413
AH-01313
Power Source
12/24VDC
24VDC
Alarm current @24VDC
15mA
12mA
Standby current
N/A
Ambient temperature
-10°C ~ +55°C
Material
Fire-proof plastic
Color
White surface / Red LED
Dimension
85mm(H) x 85mm(W) x 23mm(D)
70mm(H) x 70mm(W) x 15mm(D)
Weight
About 28g
About 32g